Modbus/BSAP Configuration

Configuring the Raven at the Polling Host for Modbus on UDP

You can use either Wireless ACE (page 10) or direct serial communication or Tel- net (page 53) to configure the modem using AT commands (page 53). This section covers standard Modbus, variations may need additional commands.

Port

The destination port for the Raven at the host needs to match the device port in use on all the Ravens at the remote sites. For example, if the remote Raven’s device port (see below) is "12345", then the Modbus host Raven's S53 destination port should be set to "12345".

In Wireless ACE, select Misc in the side menu.

FIGURE 2. Wireless ACE: Destination Port

Take note of (or set) the Device Port setting in *DPORT to configure the remote Ravens.

Relevez ou réglez (le cas échéant) le numéro du port Device des modèles Raven distants à l'aide de la commande *DPORT.

FIGURE 3. Wireless ACE: Device Port

Default Power-up Mode

The default power-up mode will need to be set. In Wireless ACE, select UDP in the side menu. Select the appropriate MD (AT commands: page 66) mode from the drop down menu.

Raven CDMA User Guide for Verizon, version 2.23

35

Page 41
Image 41
Airlink CDMA/1x manual Configuring the Raven at the Polling Host for Modbus on UDP, Port, Default Power-up Mode