TABLE 16. Modbus Settings

Command

Parameters

Details

 

 

 

IPL=n

n=0 or 1

IP List Dial

 

 

This allows access the Modbus IP list using the first two

 

 

digits of the dial string. Example: ATDT1234567 would

 

 

go to ID "12" on the Modbus list and use the associated

 

 

IP as the destination.

 

 

0 : Disabled

 

 

1 : Enabled

 

 

Cannot be configured in Wireless ACE.

 

 

 

MDhh

hh (hex byte) =

Default power-up mode.

 

00 - normal

When the PinPoint is power-cycled, it may enter the

 

mode

mode specified by this command after 5 seconds. On

 

01 - SLIP mode

startup, typing ATMD0 within 5 seconds changes the

 

mode to normal (AT command) mode.

 

02 - PPP mode

 

See also S53 to set the port for UDP or TCP.

 

03 - UDP mode

 

 

 

04 - TCP mode

 

 

07 - PassThru

 

 

mode

 

 

 

 

MLISTid=d.d.d.d

id=ID

Enters an ID and IP address into the Modbus List. ID is

 

d.d.d.d=IP or

a decimal value (1 to 100).

 

name adresse

Note: In Wireless ACE, this command (and MLISTX) is

 

 

 

 

the Addr List menu option.

 

 

 

MLISTXhexid=d.d.d.d

hexid=ID

Enters an ID and IP address into the Modbus List. ID is a

 

d.d.d.d=IP or

hexadecimal value (0 to 64).

 

name adresse

Note: This value is entered via Wireless ACE as 0xHex.

 

 

 

 

 

MVLEN=n

n= 1 or 2

Modbus Variant ID Length.

 

 

Length of the RTU ID in a modbus-variant protocol, in

 

 

bytes. This parameter is used to define the length of the

 

 

RTU ID in Modbus-like protocol data packets. This

 

 

parameter is used when the when the MD is set to hex

 

 

63.

 

 

Cannot be configured in Wireless ACE.

 

 

 

Raven CDMA User Guide for Verizon, version 2.23

83

Page 89
Image 89
Airlink CDMA/1x manual Modbus Settings, Cannot be configured in Wireless ACE, MLISTid=d.d.d.d, D.d=IP or