Section 3 Troubleshooting

No Motor Operation With AC Drive Fault(continued)

Operation

 

 

 

 

Panel

 

 

 

 

Indication

Name

Description and NOTES

Check point

Corrective action

 

 

 

 

 

 

Brake transistor

If a brake transistor fault occurs due to excessively

Check for improper

• Change the inverter.

 

alarm detection

large regenerative energy from the motor, for

braking duty.

• Please contact your

 

 

example, that fault is detected to stop the inverter

 

sales representative.

 

 

output. In this case, the inverter power must be

 

 

 

 

switched off immediately.

 

 

 

 

Note: This function is activated only when the

 

 

 

 

optional brake resistor is connected.

 

 

 

 

 

 

 

 

Output side

This function stops the inverter output if a ground

Check for a ground fault

Remedy the ground

 

ground fault

fault overcurrent flows due to a ground fault which

in the motor and

fault portion.

 

overcurrent

occurred in the inverter's output (load) side. Use Pr.

connection cable.

 

 

protection

249 "ground fault detection at start” to set whether

 

 

 

 

the protective function is to be activated or not. (In the

 

 

 

 

400V class, the protective function is always active.)

 

 

 

 

 

 

 

 

External

If the external thermal relay designed for motor

• Check for motor

Reduce the load and

 

thermal relay

overheat protection or the internally mounted

overheating.

operating duty.

 

operation

temperature relay in the motor switches on (contacts

• Check that the value of

 

 

 

open), the inverter output is stopped. If the relay

7 (OH signal) is set

 

 

 

contacts are reset automatically, the inverter will not

correctly in any of Pr.

 

 

 

restart unless it is reset.

180 to Pr. 183 (input

 

 

 

Note: This function is activated only when OH has

terminal function

 

 

 

been set to any of Pr. 180 to Pr. 183 (input terminal

selection).

 

 

 

function selection).

 

 

 

 

 

 

 

 

Stall prevention

The running frequency has fallen to 0 by stall

Check the motor for use

Reduce the load

 

 

prevention activated. (OL while stall prevention is

under overload.

weight.

 

 

being activated.)

 

 

 

 

 

 

 

 

Option alarm

Also stops the inverter output if the dedicated option

Check that the plug-in

• Connect the plug-in

 

Stops the

used in the inverter results in setting error or

option connector is

option securely.

 

inverter output

connection (connector) fault.

plugged securely.

• Please contact your

 

if the inverter

Note: Only when the FR-E5NC is fitted to the

 

sales representative.

 

station is

three-phase 400V power input model.

 

 

 

disconnected

 

 

 

 

from the system

 

 

 

 

in the NET

 

 

 

 

mode.

 

 

 

 

 

 

 

 

 

Parameter

A fault occurred in parameters stored (example:

Check for too many

Please contact your

 

storage device

E2PROM fault).

number of parameter

sales representative.

 

alarm

 

write times.

 

 

 

 

 

 

 

Parameter unit

This function stops the inverter output if

• Check for loose fitting

Fit the control panel

 

disconnection

communication between the inverter and PU is

of the control panel

(FR-PA02-o2) and

 

 

suspended, e.g. the PU is disconnected, when "2",

(FR-PA02-o2) or

FR-PU04 securely.

 

 

"3", "16" or "17" was set in Pr. 75. This function stops

FR-PU04.

 

 

 

the inverter output if the number of successive

• Check the Pr. 75 setting.

 

 

 

communication errors is greater than the number of

 

 

 

 

permissible retries when the Pr. 121 value is "9999"

 

 

 

 

for RS-485 communication from the PU connector.

 

 

 

 

 

 

 

 

Retry count

If operation cannot be resumed properly within the

Find the cause of alarm

Eliminate the cause of

 

exceeded

number of retries set, this function stops the inverter

occurrence.

the error preceding this

 

 

output.

 

error indication.

 

 

 

 

 

 

CPU error

If the arithmetic operation of the built-in CPU does

 

Please contact your

 

 

not end within a predetermined period, the inverter

 

sales representative.

 

 

self-determines it as an alarm and stops the output.

 

 

 

 

 

 

 

 

CPU error

This function stops the inverter output if a

 

Please contact your

 

 

communication error occurs in the built-in CPU.

 

sales representative.

 

 

(400V class only)

 

 

 

 

 

 

 

48