American Power Conversion Bypass Static manual SNMP Settings screen

Models: Bypass Static

1 56
Download 56 pages 51.59 Kb
Page 23
Image 23
SNMP Settings screen

UPS Display: Network Configuration Screens

Apply Changes: Select this button after all changes have been made. All entries will appear in red until Apply Changes is pressed.

Send Test E-mail: When this button is pressed, a test E-mail is sent to all configured E-mail recipients. This button can be used to validate the e-mail settings.

SNMP Settings screen

The UPS can be set to send SNMP traps if UPS alarm conditions occur, and when the conditions return to normal afterwards. Each trap contains a description of the alarm condition. Up to 10 Trap Receivers can be entered.

The Trap Receiver must have the APC PowerNet MIB (version 3.6.1 or later). The latest version of the PowerNet MIB can be downloaded from www.apc.com.

Network Settings must be configured prior to configuring the SNMP Settings.

Note

Normal

Network Configuration

5.34 PM

SNMP Settings

Enable SNMP

1 of 10 trap receivers

Trap Receiver(s)

Severity

xxx.xxx.xxx.xxInformational

Add new

Send Test SNMP

Page 3 of 5

Enable SNMP: Enable the SNMP functionality by selecting this checkbox.

To add a new Trap Receiver, touch the Add New button, type in the address and specify the minimum severity of alarm.

To edit or delete a Trap Receiver, select the recipient as they appear in the recipient list. Choose to either update or delete the Trap receiver.

Apply Changes: Select this button after all changes have been made. All entries will appear in red until Apply Changes is pressed.

Send Test SNMP: When this button is pressed, a test trap is sent to all configured Trap Receivers. This button can be used to validate SNMP settings.

Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001

17

Page 23
Image 23
American Power Conversion Bypass Static manual SNMP Settings screen