System Start-Up from Manual Bypass Operation

System Start-Up from Manual Bypass Operation

If the UPS has been operating in manual bypass operation and no power is connected to the UPS, the UPS display will be inactive. To re-start the system from manual bypass and achieve on-line operation, close Q1 in the external maintenance bypass panel. This will power up the internal power supply. Wait for the display to become active and follow the screen-prompted instructions.

CAUTION!

Follow these instructions carefully. Failure to do so could result in equipment damage.

Manual bypass/Off

Normal

UPS Summary

0:00 AM

Q2

~ ~

Q7

Q8

Select Operation/

Configuration

Select Start-up

Manual Bypass/Off

Normal

Operation

5.40 PM

Startup

Transfer from manual bypass to online

Shutdown

Transfer from online to manual bypass

Online Static Bypass

Transfer from online to static bypass

Static Bypass Online

Transfer from static bypass to online

Network Configuration

 

User Configuration

 

View Event Log

 

Predictive Maintenance

 

Follow the start-up instructions on the screen.

Manual bypass/Off

Normal

UPS Startup

5.40 PM

Close Q1

Display will be off until Q1 closed

Close breaker Q5

SSW input

 

 

Charge DC Capacitors

Initiate Charge

Close battery breakers Q7 and Q8

Connect battery

Close breaker Q2

UPS output

Initiate transfer to static bypass

Initiate transfer

Open breaker Q3

Manual bypass

Push UPS "ON" button

UPS will power up

Active commands initially appear in red. Once a command has been carried out successfully, its text will change to green. Important: After pressing “Initiate charge” in step 2, wait until the green lights go on alongside battery breakers Q7 and Q8 on front of the Battery Breaker Box before closing the breakers.

Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001

35