Transfer from Online to Static Bypass Operation

Transfer from Online to Static Bypass Operation

Follow the below procedure to transfer from Online to Static Bypass Operation:

UPS Summary

~ ~

Q7 Q8

Select Operation/Configuration Select Operation/Configuration  on UPS Summary screen Select Online -> Static Bypass on Operation screenInitiate transfer to Online -> on Online to Static Bypass screen on UPS Summary screen Online to Static Bypass

Normal

0:00 AM

Q2

Normal

Normal

Select Online -> Static Bypass on Operation screen

Press

Initiate transfer to Online -> on Online to Static Bypass screen

Operation

Startup

Transfer from manual bypass to online

Shutdown

Transfer from online to manual bypass

Online Static Bypass

Transfer from online to static bypass

Static Bypass Online

Transfer from static bypass to online

Network Configuration

 

User Configuration

 

View Event Log

 

Predictive Maintenance

 

Online to Static Bypass

Initiate transfer to static bypassInitiate transfer

In static bypass the load is powered directly by utility power. There will be no UPS backup.