UPS Start-Up Screen

From the UPS Start-Up screen, the power flow can be transferred from Manual Bypass to Online Operation.

Manual bypass/Off

Normal

UPS Startup

5.40 PM

Close Q1

Display will be off until Q1 closed

Close breaker Q5

SSW input

 

 

Charge DC Capacitors

Initiate Charge

Close battery breakers Q7 and Q8

Connect battery

Close breaker Q2

UPS output

Initiate transfer to static bypass

Initiate transfer

Open breaker Q3

Manual bypass

Push UPS "ON" button

UPS will power up

The UPS Start-Up screen shows a list of actions, which need to be completed in order to start up the UPS from Manual Bypass Operation. The actions are initially indicated in red to show that they have not yet been completed. A yellow bar will highlight the actions in the order in which they need to be completed. As actions are completed they will change to green.

The Start-Up procedure is described in “System Start-Up from Manual Bypass Operation” .

Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001