System Shutdown from Online to Manual Bypass Operation

To shut down the UPS (transfer from on-line operation to manual bypass operation), follow the screen-prompted instructions as illustrated.

CAUTION!

Do not open Q3 when the UPS is in manual bypass operation, as this action may result in a load drop or a failure of the UPS to support the load.

Normal

UPS Summary

0:00 AM

~ ~

Q2

Q7 Q8

Select Operation/

Configuration

Normal

Normal

Operation

5.40 PM

Startup

Transfer from manual bypass to online

Shutdown

Transfer from online to manual bypass

Online Static Bypass

Transfer from online to static bypass

Static Bypass Online

Transfer from static bypass to online

Select Shutdown

Network Configuration

User Configuration

View Event Log

Predictive Maintenance

Follow the shut-down instructions on the screen.

Normal

Normal

UPS Shutdown

5.40 PM

Initiate transfer to static bypass

Initiate transfer

Close breaker Q3

Load will be on manual bypass

All instructions initially appear in red. Once a command has been carried out successfully, its text will change to green.

Open breaker Q5

SSW input

Push UPS "OFF" button

UPS power down

Open breaker Q2

UPS output

Open battery breakers Q7 and Q8

Isolate UPS from battery

Open breaker Q1

UPS input

Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001

37

Page 43
Image 43
American Power Conversion Bypass Static manual System Shutdown from Online to Manual Bypass Operation