UPS Display: User Configuration Screens
•Battery monitor test: Setting this value to True results in an automatic battery monitor test being performed at regular intervals specified by the Service Engineer. The three options are:
–Auto battery test - every (N) week(s).
–Auto battery test - on one day of the week.
–Auto battery test - at a specific time of the day.
•Battery capacity test: Setting this value to True results in the batteries being discharged until a Battery Low Voltage Level is reached. This test can only be performed manually. The test is used to cycle the batteries in order to calibrate the backup time with the current load and battery modules installed.
•Battery monitor reset: In the event of a weak battery or another battery problem, use this button to reset the battery monitor.
Symmetra® MW with Internal Bypass Static Switch - User Guide - | 23 |