Operation Modes

Operation Modes

On-line Operation

During on-line operation, the critical load is supported by the inverters. The main inverter controls the output voltage and the delta inverter controls the input current. The delta inverter also provides battery-charging current. While the UPS is running in this mode, a single-line diagram will appear on the screen. The green line indicates the power flow from the utility supply through the UPS to the load.

CAUTION!

Do not open Q2 when the UPS is in on-line operation, as this action may result in a load drop or a failure of the UPS to support the load.

Bypass Static Switch

Delta inverter

Main inverter

Battery

Breaker Identification

Q1

UPS input breaker

Q5

Static bypass input breaker

 

 

 

 

Q2

UPS output breaker

Q7

Battery breaker 1

 

 

 

 

Q3

Manual bypass breaker

Q8

Battery breaker 2

 

 

 

 

Only operate a breaker when the associated breaker lamp is on.

Note

Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001

31