American Power Conversion Bypass Static manual Manual Bypass Operation

Models: Bypass Static

1 56
Download 56 pages 51.59 Kb
Page 40
Image 40
Manual Bypass Operation

Manual Bypass Operation

During manual bypass operation, the critical load is supplied directly by utility power, making it possible to isolate the UPS and the Bypass Static Switch for maintenance.

Battery power is not available as an alternate power source while the system is running in manual bypass operation.

Note

A single-line diagram will appear on the screen, with an orange line indicating the power flow from the utility to the load via the Q3 breaker.

CAUTION!

Do not open Q3 when the UPS is in manual bypass operation, as this action may result in a load drop or a failure of the UPS to support the load.

Bypass Static Switch

Delta inverter

Main inverter

Battery

Breaker Identification

Q1

UPS input breaker

Q5

Static bypass input breaker

 

 

 

 

Q2

UPS output breaker

Q7

Battery breaker 1

 

 

 

 

Q3

Manual bypass breaker

Q8

Battery breaker 2

 

 

 

 

Only operate a breaker when the associated breaker lamp is on.

Note

34

Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001

Page 40
Image 40
American Power Conversion Bypass Static manual Manual Bypass Operation