Overview
InfraStruXure PDU Components
The APC 150kW InfraStruXure PDU provides distribution and management of electrical power. The InfraStruXure PDU has the capacity of 150kW, accepts 480V or 600V 3-phase input, and distributes 208V 3-phase power to equipment racks and Rack Distribution Panels (RDPs). The RDPs sit in the top 10U of specially-designed NetShelter VX enclosures and distributes power to equipment racks. The InfraStruXure PDU is housed in a specially-designed 23-inch NetShelter VX Enclosure. Each 150kW InfraStruXure PDU has seventy-five (75) pole positions available for feeding equipment racks and three (3), three-pole positions available for feeding RDPs. Each RDP has thirty-nine (39) pole positions available for feeding equipment racks and one (1), three-pole position that back-feeds the RDP.
Rack Distribution Panel (RDP)
39 pole positions available
One, 3-pole breaker back-feeding the RDP
NetShelter VX Enclosure
42-position circuit breaker panel
75 pole positions available
150kW InfraStruXure PDU
Three circuit breakers sub-feeding the RDPs
Power cables feeding equipment racks
Sub-feed power cable feeding the RDP
150kW InfraStruXure PDU—Operation and Configuration | 5 |