Overview

InfraStruXure PDU Components

The APC 150kW InfraStruXure PDU provides distribution and management of electrical power. The InfraStruXure PDU has the capacity of 150kW, accepts 480V or 600V 3-phase input, and distributes 208V 3-phase power to equipment racks and Rack Distribution Panels (RDPs). The RDPs sit in the top 10U of specially-designed NetShelter VX enclosures and distributes power to equipment racks. The InfraStruXure PDU is housed in a specially-designed 23-inch NetShelter VX Enclosure. Each 150kW InfraStruXure PDU has seventy-five (75) pole positions available for feeding equipment racks and three (3), three-pole positions available for feeding RDPs. Each RDP has thirty-nine (39) pole positions available for feeding equipment racks and one (1), three-pole position that back-feeds the RDP.

Rack Distribution Panel (RDP)

39 pole positions available

One, 3-pole breaker back-feeding the RDP

NetShelter VX Enclosure

42-position circuit breaker panel

75 pole positions available

150kW InfraStruXure PDU

Three circuit breakers sub-feeding the RDPs

Power cables feeding equipment racks

Sub-feed power cable feeding the RDP

150kW InfraStruXure PDU—Operation and Configuration

5

Page 13
Image 13
American Power Conversion PD150G6F, PD150L6F manual Overview, InfraStruXure PDU Components