How to Add a Sub-Feed Output Circuit Breaker to the PDU and Connect a Sub-Feed Power Cable

Overview

As an option, you can add 150- or 225-amp sub-feed output circuit breakers () to the two (2) mounting bracket positions provided on your 150kW InfraStruXure PDU. These circuit breakers offer a means for distributing higher blocks of power to other equipment. If your PDU has already been configured with a subfeed breaker(s), refer to “How to connect the sub-feed cable to the circuit breaker” on page 56. To install a new circuit breaker, follow all of the instructions in this section.

The PDU must be powered down before adding a subfeed. For instructions on ensuring total power off, refer to “How to Ensure Total Power Off” on page 33 of this

Caution manual.

54

150kW InfraStruXure PDU—Operation and Configuration

Page 62
Image 62
American Power Conversion PD150L6F, PD150G6F manual Overview