Customizing and Updating the PDU

How to connect the sub-feed cable to the circuit breaker

1.Use a knockout punch to create an appropriately-sized hole in either the top or

bottom gland plate on the PDU through which you will route the sub-feed cable. Use the top gland plate for overhead wiring and the bottom gland plate for underfloor wiring.

2. Re-attach the gland plate.

3. Install the conduit, fitting, and lock-nut.

4. Thread the sub-feed cable through the conduit and to the circuit breaker.

5. Connect the three-phase wires to the load side of the circuit breaker.

6.Connect the sub-feed neutral wire to the neutral bar on the panel (M8 studs are provided).

7.Connect the ground wire to one of the ground studs on the panel bracket (M8 studs are provided).

56

150kW InfraStruXure PDU—Operation and Configuration

Page 64
Image 64
American Power Conversion PD150L6F, PD150G6F manual How to connect the sub-feed cable to the circuit breaker