Overview: InfraStruXure PDU

Rear view (interior)

The PDU monitoring unit receives signals from several current and voltage monitoring boards that report to a central board assembly located in the PDU monitoring unit. The monitoring unit has one 10 Base-T (Cat-5) connection to the Information Controller Hub (or switch), four relay output connections, four input contact connections, and one EPO input connection. Make these connections at the user connection plate located on the roof of the PDU. See “PDU monitoring unit” on page 10 for a more detailed description.

The Main Input breaker connects to your main power source. The breaker accepts 480V input and requires 3-wire input conductors.

150kW InfraStruXure PDU—Operation and Configuration

9

Page 17
Image 17
American Power Conversion PD150G6F, PD150L6F manual Rear view interior