Connect the EPO

Connect the EPO to the UPS and the XR Battery Enclosure

1.Connect the EPO (Emergency Power Off) to J108 in the UPS and to J203 in the XR Battery Enclosure by guiding the cable through conduits.

2.Connect the EPO by using this configuration:

+24 V Normally open

UPS

J108

1EPO circuit

2

XR

J203

1EPO circuit

2

EPO is activated when an external 24 VDC, 1500 mA is supplied on pin 1 with reference to pin 2

See “EPO requirements” on page 23.

Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation

19