APC 10-40 KVA 380/400/415 V Specifications, Battery voltage and current, Recommended cable sizes

Models: 10-40 KVA 380/400/415 V

1 32
Download 32 pages 51.01 Kb
Page 27
Image 27

Specifications

Battery voltage and current

XR Battery Enclosure

30 kVA

40 kVA

 

 

 

Battery voltage (nominal)

± 192 VDC

± 192 VDC

 

 

 

Battery current (at full load)

69.4 A at ± 192 V

87.9A at ± 192V

 

 

 

Max. current (at end of discharge)

86.6 A at ± 154 V

110.1A at ± 154V

 

 

 

If the XR Battery Enclosure is customer-supplied, please refer

 

 

to product-specific data.

 

 

 

 

 

Recommended cable sizes

North America

Europe, Middle East, Asia

Japan

 

 

 

208/220 V

380/400/415 V

200/208 V

 

 

 

BAT+, N, BAT- 1 AWG 167º F

BAT+, N, BAT- 50 mm2 75º C

BAT+, N, BAT- 50 mm2 75º C copper

(75º C) copper wire

(167º F) copper wire

wire.

 

 

Use only 8,08-1,3 mm2 copper wire rated

 

 

minimum 250 V.

 

 

 

Note: Power terminal lug diameter: minimum 6 mm (0.2 in).

Torque value: 45 lbf-in/7 Nm.

Note: Use Molex lug type or equivalent, and follow the manufacturer’s specifications.

EPO requirements

SELV voltage

Current:

24 VDC

1500 mA

Torque specification

Torque specification: Isolators: M5 7 Nm (45 lbf-in).

Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation

23

Page 27
Image 27
APC 10-40 KVA 380/400/415 V manual Specifications, Battery voltage and current, Recommended cable sizes, EPO requirements