Parallel System
• Q1: Utility/mains input
•Q2: UPS output
• Q3: Manual bypass
• Q4: System output
• Q5: Static bypass input
Fuse and Breaker Sizes in Single Systems
| 10 kVA | 15 kVA | 20 kVA | 30 kVA |
|
|
|
|
|
Utility input Q1 | 35 A | 60 A | 80 A | 110 A |
|
|
|
|
|
Static bypass input | 35 A | 60 A | 80 A | 110 A |
Q5 |
|
|
|
|
UPS output Q2 | 35 A | 60 A | 80 A | 110 A |
|
|
|
|
|
Manual bypass Q3 | 35 A | 60 A | 80 A | 110 A |
Fuse and Breaker Sizes in Parallel Systems
Q3 and Q4 in Parallel Capacity Systems
Units in parallel | 10 kVA | 15 kVA | 20 kVA | 30 kVA |
|
|
|
|
|
2 | 70 A | 110 A | 150 A | 225 A |
|
|
|
|
|
3 | 110 A | 175 A | 225 A | 350 A |
|
|
|
|
|
4 | 150 A | 225 A | 300 A | 450 A |
|
|
|
|
|
Q3 and Q4 in Redundant Parallel Systems (n+1)
Units in parallel | 10 kVA | 15 kVA | 20 kVA | 30 kVA |
|
|
|
|
|
2 | 35 A | 60 A | 80 A | 110 A |
|
|
|
|
|
3 | 70 A | 110 A | 150 A | 225 A |
|
|
|
|
|
4 | 110 A | 175 A | 225 A | 350 A |
|
|
|
|
|
6 | MGE™ Galaxy™ 3500 |