Minimum Breaker Settings
|
| 800% overload | 150% overload | 125% overload | Continuously |
|
| bypass | normal/battery | normal/battery |
|
|
| operation | operation | operation |
|
| Duration | 500 ms | 60 s | 10 min |
|
|
|
|
|
|
|
10 kVA | Mains input | - | - | 34 A | |
| Static bypass | 223 A | - | - | 31 A |
| input |
|
|
|
|
| UPS output | 223 A | 42 A | 35 A | 31 A |
|
|
|
|
|
|
15 kVA | Mains input | - | - | 51 A | |
| Static bypass | 333 A | - | - | 46 A |
| input |
|
|
|
|
| UPS output | 333 A | 63 A | 52 A | 46 A |
|
|
|
|
|
|
20 kVA | Mains input | - | - | 68 A | |
| Static bypass | 444 A | - | - | 62 A |
| input |
|
|
|
|
| UPS output | 444 A | 84 A | 70 A | 62 A |
|
|
|
|
|
|
30 kVA | Mains input | - | - | 99 A | |
| Static bypass | 667 A | - | - | 92 A |
| input |
|
|
|
|
| UPS output | 667 A | 125 A | 105 A | 92 A |
|
|
|
|
|
|
1 For single mains systems, use the higher value of mains and static bypass
7 |