Connect Battery Power in Installations with Busbars

WARNING: Before carrying out the steps below, the system must be in total power off and the batteries must be removed.

Isolator Installation Principle

The isolators separate the baying kit busbar from the six vertical busbars in each XR Battery Enclosure, and the (+), N, and (-) busbars in the UPS.

1.Guide the busbar with isolator through the adjacent side panels.

2.Position the isolators across the vertical busbars (N in this example) and then fasten the isolator busbar by using the provided M5 Torx screws.

3.Secure the isolator to its busbar with cable ties.

990-1957C-001 MGE™ Galaxy™ 3500 10-30 kVA 208/220 V Single and Parallel Installation