Install Busbars in 523 mm (20.59 in) UPS System with the UPS Placed to the Left (seen from the front)

1.Install the following baying kit busbars between the UPS and XR1:

880-1607 between vertical busbar N on the UPS and busbar 4 on XR1

880-1606 between vertical busbar (+) on the UPS and busbar 1 on XR1 880-1605 between busbar (-) on the UPS and busbar 6 on XR1

2.Install the following baying kit busbars between the two XR Battery Enclosures: 880-0926 between vertical busbar 3 on XR1 and busbar 4 on XR2

880-0940 between vertical busbar 2 on XR1 and busbar 1 on XR2 880-0941 between vertical busbar 5 on XR1 and busbar 6 on XR2

18

MGE™ Galaxy™ 3500 10-30 kVA 208/220 V Single and Parallel Installation 990-1957C-001