6.Insert the interconnection plates between the two enclosures. One is positioned toward the front and the other toward the rear. Notice how the “wings” on the interconnection plates rest in slots at the top of the inner panel.

7.Align the two enclosures and level the three marked rows of bolt holes in UPS 1 with the holes in UPS 2.

8.Push the two enclosures firmly together.

9.Bolt the two enclosures together using the six M6x25 mm screws and nuts supplied in the kit; join one hole at the front and one hole at the rear of the enclosures on three levels.

10.Position the third U-shaped floor anchoring bracket under the adjacent enclosure (see previous graphics) and insert a minimum of two floor anchoring M8 screws (not provided) through the holes in the bottom of the enclosure and through the holes in the U-shaped floor anchoring bracket, and into the predrilled floor holes, and then fasten the screws.

990-1957C-001 MGE™ Galaxy™ 3500 10-30 kVA 208/220 V Single and Parallel Installation

15