Install Busbars in 352 mm (13.85 in) UPS System with the UPS Placed to the Left (seen from the front)

1.Install the following baying kit busbars between the UPS and XR1:

880-1604 between vertical busbar N on the UPS and busbar 3 on XR1

880-1604 between vertical busbar (+) on the UPS and busbar 1 on XR1 880-0939 between vertical busbar (-) on the UPS and busbar 6 on XR1

2.Install the following baying kit busbars between two XR Battery Enclosures: 880-0926 between vertical busbar 4 on XR1 and vertical busbar 3 on XR2 880-0941 between vertical busbar 2 on XR1 and vertical busbar 1 on XR2 880-0940 between vertical busbar 5 on XR1 and vertical busbar 6 on XR2