Prepare for Cables

Bottom Cable Entry

1.From the rear of the UPS, loosen the six M4 screws from the upper cover (the cable landing area), and remove. Save the screws for later use

2.Loosen the two M4 screws (one on each side) from the top part of the conduit box. Loosen the M4 screws attaching it to the bottom part (two screws in 352 mm (13.8 in) enclosure three screws in a 523 mm (20 in) enclosure) and remove. Save the screws for later use.

3.Loosen the four M4 screws (two on each side) from the conduit box and remove. Save the screws for later use.

4.Punch as many holes as needed in the marked areas of the bottom conduit box.

5.Attach the conduit box bottom to the enclosure (reuse the screws from step 3).

6.Attach conduits to the conduit box.

7.Run the cables through the conduits, the bottom of the conduit box, and up into the cable landing area.

A.Bypass

B.Output

C.Battery

D.Input

8.Attach conduit box top to the conduit box bottom and to the enclosure reusing the screws from step 2.

9.Fasten the cables with cable ties.

990-1957C-001 MGE™ Galaxy™ 3500 10-30 kVA 208/220 V Single and Parallel Installation

27