EPO in Single Systems
Connect the EPO cable using one of the following four wiring configurations.
Note: Use only
Note: The UPS must be connected to either a dry contact or a 24 VDC EPO (Emergency Power Off) switch.
Note: The external EPO +24 VDC, 1500 mA circuit can be supplied through other vendors.
1. Dry Contacts Normally Open: EPO is activated when pin 1 is connected to pins 3 and 5. Connections:
2. +24 V Normally Open: EPO is activated when an isolated SELV 24 VDC voltage is supplied on pin 1 with reference to pin 2. Connections:
3. Dry Contacts Normally Closed: EPO is activated when a connection from pin 3 to 5 is opened. Connections:
4. +24 V Normally Closed: EPO is activated when a SELV 24 VDC voltage is removed from pin 3 with reference to pin 4.
32 | MGE™ Galaxy™ 3500 |