Specifications
WARNING: The UPS must be supplied from a 208/120 V or 220/127 V 4W + GND 60 HZ source.
AC Input Specifications
| 10 kVA |
| 15 kVA |
| 20 kVA |
| 30 kVA |
|
|
|
|
|
|
|
|
|
|
| 208 V | 220 V | 208 V | 220 V | 208 V | 220 V | 208 V | 220 V |
|
|
|
|
|
|
|
|
|
Connection type |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
Input frequency |
|
|
|
|
|
|
| |
(Hz) |
|
|
|
|
|
|
|
|
I thd | < 5% at full load |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
Nom input current | 24.3 | 23.0 | 36.6 | 34.6 | 48.6 | 45.8 | 73.2 | 69.0 |
(A) |
|
|
|
|
|
|
|
|
Max input current | 26.7 | 25.2 | 40.2 | 38.0 | 53.0 | 50.1 | 80.1 | 75.8 |
(A) |
|
|
|
|
|
|
|
|
Input current | 32.8 | 32.8 | 49.5 | 49.5 | 65.2 | 65.2 | 98.8 | 98.8 |
limitation (A) |
|
|
|
|
|
|
|
|
Input power factor | > 0.98 at load > 50% |
|
|
|
|
|
| |
correction |
|
|
|
|
|
|
|
|
Maximum Short | 30 |
|
|
|
|
|
|
|
Circuit Withstand |
|
|
|
|
|
|
|
|
(kA) |
|
|
|
|
|
|
|
|
AC Bypass Input Specifications
| 10 kVA |
| 15 kVA |
| 20 kVA |
| 30 kVA |
|
|
|
|
|
|
|
|
|
|
| 208 V | 220 V | 208 V | 220 V | 208 V | 220 V | 208 V | 220 V |
|
|
|
|
|
|
|
|
|
Connection type |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
Input frequency | 50 +/- 10 or 60 +/- 10 |
|
|
|
|
|
| |
(Hz) |
|
|
|
|
|
|
|
|
Nom input current | 27.8 | 26.2 | 41.6 | 39.4 | 55.5 | 52.5 | 83.3 | 78.7 |
(A) |
|
|
|
|
|
|
|
|
2 | MGE™ Galaxy™ 3500 |