1.Feed the cable up through the conduit box on XR1 or through the transparent cable route bracket (not shown) to the cable connection area.

2.Connect the (-) cable to busbar no. 5 (-), the N cable to busbar no. 3 (N), the (+) cable to busbar no. 2 (+) in XR1, and the ground cable to the terminal in the top of the cabinet.

3.Secure the cable to the perforated bracket with cable ties.

4.Equip the cable with conduits (if applicable).

5.Feed the cable up into the conduit box (optional for 400 V versions) on XR2.

6.Connect the (-) cable to busbar no. 6 (-), the N cable to busbar no. 4 (N), and the (+) cable to busbar no.1 (+) in XR2, and the ground cable to the terminal in the top of the cabinet. Bundle the cables using the supplied cable ties.

7.Secure the cable to the perforated bracket with cable ties.

8.Attach the top part of the conduit box (if applicable).

24

MGE™ Galaxy™ 3500 10-30 kVA 208/220 V Single and Parallel Installation 990-1957C-001