Overview of Pin Connections

J108 pin connections: 1: Normally open EPO

2: Normally open EPO return

3: Normally closed EPO

4: Normaly closed EPO return

5: +24 V SELV supply

6: SELV ground

J106 pin connections:

8: Ext. charging control return

7: External control of charging

6: Q3 active return

5: Q3 active

4: Battery measurement supply*

3: Battery unit quantity*

2: Max. battery temperature*

1: Battery measurement return*

* Should be used with APC XR Battery Enclosures

J106

Pins 1 to 4 are for battery measurement (only applicable to MGE Galaxy 3500 XR Battery Enclosures).

Pins 5 and 6 are for external maintenance bypass Q3 (auxiliary switch N/C type). When Q3 is closed, signals are fed back to the UPS controller.

Pins 7 and 8 are for external charge control. When 7 and 8 are closed, the UPS charges batteries with a pre-defined percentage (0–25–50–75–100%) of the maximum charging power. To be used in generator applications, or if special codes require control of charging. When Q3 is closed, signals are fed back to the UPS controller.

990-1957C-001 MGE™ Galaxy™ 3500 10-30 kVA 208/220 V Single and Parallel Installation