Perform a Total Power Off

WARNING: This procedure will disconnect the load.

Note: If shutdown via the display is disabled, then you cannot perform this procedure and

the message: Command not allowed, UPS configured to never shutdown appears. If you want to enable shutdown via the display, this is done by a Field Service Engineer via the UPSTuner.

1.Select UPS and press ENTER.

→ UPS

Alarm

Power Dist

Log

Switch Gear

Admin

Environment

Help

2.Select UPS Power Control and press ENTER.

→ UPS Power Control

UPS Status

UPS Tests & Diags

UPS Configuration

3.Select Turn UPS Off and press ENTER.

→ Turn UPS Off Reboot UPS

UPS into Bypass UPS to Sleep

4.Select No, Don’t Notify to shut down without delay and press ENTER.

Note: This action will cut all power to the load without shutting it down first. If you want to shut down the servers first, then choose Yes, Notify Servers. Note that this function

is only available for servers with PowerChute.

5.Confirm YES, Turn UPS Off and press

ENTER.

Notify PowerChute ?

Cancel

Yes, Notify Servers

→ No, Don't Notify

Turn UPS off Without Server Notification? > NO, ABORT

→> YES, Turn UPS Off

6.Wait for the UPS to turn off.

Turning UPS off,

please wait...

8

Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation

990–3015E-001