Start the System after Total Power Off
1.Set the upstream utility/mains power to the ON or LOCKED IN position. If the UPS has a dual mains supply, set both supplies to the ON or LOCKED IN position.
2.Set the DC DISCONNECT switch to the ON position on all XR Battery Enclosures and the
3.Set the Q1 switch to the ON position.
4.Set the SYSTEM ENABLE switch on the UPS to the ON position.
Note: Wait approximately two minutes for the system to start.
5.Set the Q5 breaker to the ON position (if applicable).
Note: The H2 LED next to the Q2 switch will turn on, indicating that it is safe to operate the Q2 switch.
6.Set the Q2 switch on the PDU,
7.Select UPS and press ENTER.
→ UPS | Alarms |
Power Dist | Log |
Switch Gear | Admin |
Environment | Help |
8.Select UPS Power Control and press ENTER.
→ UPS Power Control
UPS Status
UPS Tests & Diags
UPS Configuration
9.Select Turn UPS On and press ENTER.
→ Turn UPS On
UPS On Into Bypass
10 | Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation |