Display Message

Meaning

Corrective Action

 

 

 

No Power Modules Detected

No power modules are available.

Option 1: Ensure that the power

 

 

modules are properly installed, the

 

 

two fastening screws are tight, and

 

 

the locking latch is engaged.

 

 

Option 2: Check for other

 

 

communication alarm messages in

 

 

the log.

Not Synchronized Fault

System cannot synchronize to AC

Option 1: Decrease the sensitivity

 

line and bypass mode may not be

to input frequency.

 

available.

Option 2: Correct the input

 

 

voltage to provide acceptable

 

 

voltage/frequency.

Output Voltage Not In Range

The output voltage is not within the

Evaluate the threshold setting.

 

specified range.

If necessary, adjust it for your

 

 

situation. Contact Schneider Electric

 

 

Customer Support (see the back

 

 

cover).

Overload

The load has exceeded the system

Option 1: Decrease the load.

 

power capacity.

Option 2: Add a power module to

 

 

the system.

Power Failure

The input voltage is not acceptable

Contact Schneider Electric Customer

 

for normal operation.

Support (see the back cover).

Power Module Fault

A power module has failed and

Replace power module. See

 

requires replacement.

“Replace a Power Module“.

Redundancy Alarm

Actual power module redundancy

Option 1: If possible, install

 

has fallen below user-specified

additional power modules. See

 

redundancy alarm threshold. At

“Replace a Power Module“.

 

least one power module has failed,

Option 2: Replace failed modules.

 

or the load has increased.

See “Replace a Power Module“.

 

 

Option 3: Reduce the load.

 

 

Option 4: Change alarm limit.

Redundancy Lost

The UPS no longer detects redundant

Option 1: If possible, install

 

power modules. One or more power

additional power modules. See

 

modules have failed, or the load has

“Replace a Power Module“.

 

increased.

Option 2: Replace failed modules.

 

 

See “Replace a Power Module“.

 

 

Option 3: Reduce the load.

 

 

Option 4: Change alarm limit.

Redundant Intelligence Module

The redundant intelligence module

Contact Schneider Electric Customer

Fault

has failed and requires replacement.

Support (see the back cover).

Redundant Intelligence Module in

The main intelligence module has

Contact Schneider Electric Customer

Control

failed, and the redundant intelligence

Support (see the back cover).

 

module is functioning as the primary

 

 

intelligence module.

 

Replacement Battery Needed

One or more battery units needs to

Replace battery unit(s). See

 

be replaced.

“Replace a Battery“.

Runtime Alarm

The predicted runtime is lower than

Option 1: Install additional battery

 

the user-specified minimum runtime

modules. See “Replace a Battery“

 

alarm threshold. At least one battery

Option 2: Replace failed battery

 

module has failed or the load has

modules. See “Replace a Battery“

 

increased.

Option 3: Reduce the load.

 

 

Option 4: Change alarm limit.

Site Wiring Fault

There is a problem with the phase

Contact the certified electrician that

 

rotation or a phase is missing in the

installed the system.

 

input voltage to the UPS.

 

Static Bypass Switch Module Fault

The static bypass switch module has

Contact Schneider Electric Customer

 

failed and requires replacement.

Support (see the back cover).

34

Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation

990–3015E-001