PDU XR (if applicable) and on the main frame (only PX 48).
Return to Normal Operation from Maintenance Bypass Operation
1. Set the DC DISCONNECT switch to the ON position on all XR Battery Enclosures and the
2. Set the Q1 switch to the ON position.
3. Set the SYSTEM ENABLE switch on the UPS to the ON position.
Note: Wait approximately two minutes for the system to start.
4.Set the Q5 breaker to the ON position (if applicable).
5.Use the display interface to turn the UPS load on.
6.Select UPS and press ENTER.
→ UPS | Alarms |
Power Dist | Log |
Switch Gear | Admin |
Environment | Help |
7.Select UPS Power Control and press ENTER.
→ UPS Power Control
UPS Status
UPS Tests & Diags
UPS Configuration
16 | Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation |