Turn the UPS Load Off
1.Select UPS and press ENTER.
→ UPS | Alarms |
Power Dist | Log |
Switch Gear | Admin |
Environment | Help |
2.Select UPS Power Control and press ENTER.
→ UPS Power Control
UPS Status
UPS Tests & Diags
UPS Configuration
3.Select Turn UPS Off and press ENTER.
→ Turn UPS Off
Reboot UPS
UPS Into Bypass
UPS To Sleep
4.Select No, Don’t Notify and press ENTER.
Note: This action will cut all power to the load without shutting it off first. If you want to shut down the servers first, then choose Yes, Notify Servers.Note that this function
is only available for servers with PowerChute.
5.Confirm YES, Turn UPS Off and press
ENTER.
Notify PowerChute?
Cancel
Yes, Notify Servers
→ No, Don't Notify
Turn UPS Off Without
Server Notification?
>NO, ABORT
→ YES, Turn UPS Off
6.Wait for the UPS to turn off.
Turning UPS off,
please wait...
12 | Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation |