Turn the UPS Load Off

1.Select UPS and press ENTER.

→ UPS

Alarms

Power Dist

Log

Switch Gear

Admin

Environment

Help

2.Select UPS Power Control and press ENTER.

→ UPS Power Control

UPS Status

UPS Tests & Diags

UPS Configuration

3.Select Turn UPS Off and press ENTER.

→ Turn UPS Off

Reboot UPS

UPS Into Bypass

UPS To Sleep

4.Select No, Don’t Notify and press ENTER.

Note: This action will cut all power to the load without shutting it off first. If you want to shut down the servers first, then choose Yes, Notify Servers.Note that this function

is only available for servers with PowerChute.

5.Confirm YES, Turn UPS Off and press

ENTER.

Notify PowerChute?

Cancel

Yes, Notify Servers

→ No, Don't Notify

Turn UPS Off Without

Server Notification?

>NO, ABORT

→ YES, Turn UPS Off

6.Wait for the UPS to turn off.

Turning UPS off,

please wait...