Modular Distribution Fault List

The display interface will identify the number of the power distribution modules that has caused an alarm or warning.

Display Message

Meaning

Corrective Action

 

 

 

High Module Current Alarm

The threshold of the high module

Evaluate the threshold setting. If

 

current has been exceeded.

necessary, adjust it for your situation.

High Subfeed Current Alarm

The threshold of the high subfeed

Evaluate the threshold setting. If

 

current has been exceeded.

necessary, adjust it for your situation.

Low Module Current Alarm

The threshold of the low module

Evaluate the threshold setting. If

 

current has been exceeded.

necessary, adjust it for your situation.

Low Subfeed Current Alarm

The threshold of the low subfeed

Evaluate the threshold setting. If

 

current has been exceeded.

necessary, adjust it for your situation.

Max Module Current Alarm

The threshold of the maximum

Evaluate the threshold setting. If

 

module current has been exceeded.

necessary, adjust it for your situation.

Max Subfeed Current Alarm

The threshold of the maximum

Evaluate the threshold setting. If

 

subfeed current has been exceeded.

necessary, adjust it for your situation.

Min Module Current Alarm

The threshold of the minimum

Evaluate the threshold setting. If

 

module current has been exceeded.

necessary, adjust it for your situation.

Min Subfeed Current Alarm

The threshold of the minimum

Evaluate the threshold setting. If

 

subfeed current has been exceeded.

necessary, adjust it for your situation.

Communication Lost With Metering

Communication has been lost with

Check the communication cables

Board Alarm

the power distribution module.

to ensure that they are properly

 

 

connected. Contact Schneider

 

 

Electric Customer Support (see the

 

 

back cover).

Module Breaker Open Alarm

A modular circuit breaker is open.

Check the modular circuit breakers

 

 

to see if one has been over-loaded.

 

 

Replace if necessary.

Subfeed Breaker Open Alarm

A subfeed circuit breaker is open.

Check the subfeed circuit breakers

 

 

to see if one has been over-loaded.