Change the Date and Time
1.Select Admin and press ENTER.
UPS | Alarms |
Power Dist | Log |
Switch Gear | → Admin |
Environment | Help |
2.Select Date/Time and press ENTER.
Network Setup
Local Interface
→ Date/Time
Device ID
3.Select Date or Time and change the settings by using the UP and DOWN arrow keys. Press ENTER to save the changes.
Mode: Manual
Format: mm/dd/yyyy
Date: xx/xx/xxxx
Time: xx:xx:xx
Configure Input Contacts
1.Select Environment and press ENTER.
UPS | Alarms |
Power Dist | Log |
Switch Gear | Admin |
→ Environment | Help |
|
|
2.Select Input Contacts and press ENTER.
→ Input Contacts
Output Relays
Alarm Relay Map
3.Select desired output relay, 1 through 4, select Configuration, and press ENTER.
Input Contact:xof4 <contact name> Status: Normal
→ Configuration
4.Change the settings for name/location, alarms,
severity, and normal state. | Name/Location x |
| |
| Alarms: Enabled |
| Severity: Critical |
| Normal: Open |
22 | Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation |