Note: When replacing batteries, always replace both batteries A+B or C+D (see illustration above) as they are interconnected in pairs.

For four batteries in a row it is recommended to replace all four at the same time to ensure optimal run-time (Example 1). The batteries can also be replaced in twos, but always A+B (Example 2) or C+D (Example 3).

For two batteries in a row, always replace both batteries at the same time (Example 4).

Four batteries in a row

 

Column A

Column B

Column C

Column D

 

 

 

 

 

Example 1 –

New

New

New

New

Recommended

 

 

 

 

Example 2

New

New

Old

Old

– Minimum

 

 

 

 

requirement

 

 

 

 

Example 3

Old

Old

New

New

– Minimum

 

 

 

 

requirement

 

 

 

 

Two batteries in a row

 

Column A

Column B

Example 4

New

New

Minimum requirement

Note: Allow batteries a 24-hour recharging period after system start-up/battery replacement for battery monitoring data to become fully reliable.

30

Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation