9.Select UPS and press ENTER.

→ UPS

Alarms

Power Dist

Log

Switch Gear

Admin

Environment

Help

10.Select UPS Power Control and press ENTER.

→ UPS Power Control

UPS Status

UPS Tests & Diags

UPS Configuration

11.Select Turn UPS Off and press ENTER.

→ Turn UPS Off Reboot UPS UPS into Bypass UPS to Sleep

12.Select No, Don’t Notify and press ENTER.

Notify PowerChute ?

Cancel

Yes, Notify Servers

→ No, Don't Notify

13.Confirm by selecting YES, Turn UPS Off and press ENTER.

Turn UPS Off Without

Server Notification?

>NO, ABORT

→ >YES, Turn UPS Off

14.Wait for the UPS to turn off.

Turning UPS off,

please wait....

15. Set the UPS SYSTEM ENABLE switch to the OFF position.

16. Set the Q1 switch to the OFF position.

17. Set the Q5 breaker to the OFF position (if applicable).

18. Set the DC DISCONNECT switch to the OFF XR Battery Enclosures/PDU-XRposition on all XR Battery Enclosures and the

990–3015E-001

Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation

15