Troubleshooting

WARNING: Only trained persons familiar with the construction and operation of the equipment, as well as the electrical and mechanical hazards involved, may install and remove system components.

Status and Alarm Messages

This section lists the status and alarm messages that the UPS might display. The messages are listed in alphabetical order, and a suggested corrective action is listed with each alarm message to help you troubleshoot problems.

Note: Contact Schneider Electric Customer Support if you see alarm or status messages that are not listed here.

Note: If a problem is reported, ensure that the system component in question is correctly installed.

Display Messages
Display MessageMeaningCorrective Action

 

 

 

Battery Charger Fault

The battery charger is not

Contact Schneider Electric Customer

 

functioning properly.

Support (see the back cover).

Battery Defective

The battery capacity is estimated to

Replace battery. See “Replace a

 

be below 50% of the expected.

Battery“.

Battery Fault

A battery module has failed and

Replace battery. See “Replace a

 

requires replacement.

Battery“.

Battery High Temperature Violation

The temperature of one or more

Ensure that the ambient temperature

 

battery units has exceeded system

meets the specifications of the

 

specifications.

system. If the ambient temperature

 

 

is below 40 °C (104 °F), then initiate

 

 

a self-test to detect any bad battery

 

 

units. Replace any bad battery units.

Battery High Voltage Violation

The battery voltage is too high and

Contact Schneider Electric Customer

 

the charger has been deactivated.

Support (see the back cover).

Battery Monitor Card Fault

The battery monitor card has failed.

Contact Schneider Electric Customer

 

 

Support (see the back cover).

Battery Monitor Card Removed

The battery monitor card has been

Contact Schneider Electric Customer

 

removed.

Support (see the back cover).

Battery Weak

The battery capacity is estimated to

Replace battery. See “Replace a

 

be below 75% of the expected.

Battery“.

Contact APC for secure start-up

The UPS has been running 5 days.

Contact Schneider Electric Customer

 

start-up check by an Schneider

Support (see the back cover).

 

Electric Field Service Engineer

 

 

(FSE) is recommended.

 

Discharged Battery

The UPS is online and the battery

No corrective action necessary.

 

charge is low.

Note: If the input voltage fails,

 

 

runtime will be limited.

32

Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation

990–3015E-001