Display Message | Meaning | Corrective Action |
|
|
|
Static Bypass Switch Module | The system no longer detects a static | Option 1: Ensure that the static |
Removed | bypass switch module. | bypass switch module is installed |
|
| properly. |
|
| Option 2: Call Schneider Electric |
|
| Customer Support for replacement |
|
| of the static bypass switch module. |
|
|
|
System in Maintenance Bypass | The system is in maintenance | No corrective action necessary. |
| bypass: the Q2 breaker is open and |
|
| the Q3 breaker is closed. |
|
System Power Supply Card Fault | The system power supply card has | Ensure that the power supply card is |
| failed and requires replacement. | installed properly. See “Replace a |
|
| Power Management Card“. |
System | The system configuration download | Check for other alarms and contact |
| has failed. Unable to determine the | Schneider Electric Customer |
| system voltage or frame size. | Support (see the back cover). |
Technical check recommended | Regular maintenance requirements | Contact Schneider Electric Customer |
| and the end of service life | Support (see the back cover). |
| consumable components. |
|
Warranty expiring soon | The end of the contractual legal | Contact Schneider Electric Customer |
| warranty. | Support (see the back cover). |