ENTER.
Turn UPS On
→ UPS On into Bypass
9.Select Continue Turn On and press ENTER.
Battery
→ >Continue Turn On
10.Confirm by selecting Yes, On Into Bypass and press ENTER.
Confirm:
UPS on Into Bypass >NO, ABORT
→ >Yes, On Into Bypass
11.Wait for the UPS to turn the load on.
Turning UPS on Into
Bypass.
Please wait...
12.The UPS is now ON.
Note: The H2 LED next to the Q2 switch will turn on, indicating that it is safe to operate the Q2 switch.
13.Set the Q2 switch on the PDU,
Note: The H3 LED next to the Q3 switch will turn on, indicating that it is safe to operate the Q3 switch.
14.Set the Q3 switch to the OFF position.
15.Use the display interface to transfer the UPS out of bypass:
16.Select UPS and press ENTER.
UPS’s output is now in bypass
Press any key...
→ UPS | Alarms |
Power Dist | Log |
Switch Gear | Admin |
Environment | Help |
17.Select UPS Power Control and press ENTER.
→ UPS Power Control
UPS Status
UPS Tests & Diags
UPS Configuration
Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation | 17 |