8.Select Turn UPS On into Bypass and press

ENTER.

Turn UPS On

→ UPS On into Bypass

9.Select Continue Turn On and press ENTER.

Battery back-up not available in bypass! >Cancel

→ >Continue Turn On

10.Confirm by selecting Yes, On Into Bypass and press ENTER.

Confirm:

UPS on Into Bypass >NO, ABORT

→ >Yes, On Into Bypass

11.Wait for the UPS to turn the load on.

Turning UPS on Into

Bypass.

Please wait...

12.The UPS is now ON.

Note: The H2 LED next to the Q2 switch will turn on, indicating that it is safe to operate the Q2 switch.

13.Set the Q2 switch on the PDU, PDU-XR or the external maintenance bypass panel to the ON position.

Note: The H3 LED next to the Q3 switch will turn on, indicating that it is safe to operate the Q3 switch.

14.Set the Q3 switch to the OFF position.

15.Use the display interface to transfer the UPS out of bypass:

16.Select UPS and press ENTER.

UPS’s output is now in bypass

Press any key...

→ UPS

Alarms

Power Dist

Log

Switch Gear

Admin

Environment

Help

17.Select UPS Power Control and press ENTER.

→ UPS Power Control

UPS Status

UPS Tests & Diags

UPS Configuration

990–3015E-001

Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation

17