Display Message

Meaning

Corrective Action

 

 

 

Extended Run Frame Fault

One of the battery enclosures has

Contact Schneider Electric Customer

 

failed.

Support (see the back cover).

External DC Disconnect Switch

The external DC DISCONNECT

Close the external DC

Open

switch tripped. Battery power is not

DISCONNECT switch. If the

 

available or the runtime is lower

problem continues, call Schneider

 

than expected.

ElectricCustomer Support.

External Switch Gear

The external switch gear

Contact Schneider Electric Customer

Communication Card Fault

communication card has failed.

Support (see the back cover).

External Switch Gear

The system no longer detects an

Option 1: Ensure the external

Communication Card Removed

external switch gear communication

switch gear communication card is

 

card.

installed properly.

 

 

Option 2: Contact Schneider

 

 

Electric Customer Support (see the

 

 

back cover).

Graceful Shutdown Initiated

A graceful shutdown or reboot

No corrective action necessary.

 

has been initiated from the display

 

 

interface or other accessory.

 

Internal Communication Bus Fault

One of the buses used for

Contact Schneider Electric Customer

 

communication between the

Support (see the back cover).

 

UPS modules has failed.

 

In Bypass: Hardware Fault

The system has transferred into

Contact Schneider Electric Customer

 

bypass because a fault has occurred.

Support (see the back cover).

In Bypass: Overload

The system has transferred into

Option 1: Decrease the load.

 

bypass because the load has

Option 2: Add a power module to

 

exceeded the power capacity of the

the system.

 

system.

 

In Bypass: User-Initiated

The system has been transferred into

Check for any problems with the

 

bypass due to user action.

system.

 

 

Transfer the system to normal

 

 

operation.

Input Voltage or Frequency Cannot

The frequency or voltage is out

Correct the input voltage to provide

Support Bypass

of acceptable range for bypass.

acceptable voltage or frequency.

 

This message occurs when the

 

 

UPS is online, and indicates that

 

 

bypass mode may not be available

 

 

if required.

 

Intelligence Module Fault

The main intelligence module has

Contact Schneider Electric Customer

 

failed and requires replacement.

Support (see the back cover).

Load (kVA) Alarm Violation

The load has exceeded the user

Option 1: Use the display interface

 

specified load alarm threshold.

to raise the alarm threshold.

 

 

Option 2: Reduce the load.

Local Management-To-UPS

Internal communications in the

Contact Schneider Electric Customer

Communication Lost

system have failed.

Support (see the back cover).

Low Battery

The UPS is in battery operation and

Runtime is limited. Shut down the

 

the battery charge is low.

system and the load equipment or

 

 

restore the input voltage.

No Batteries Detected

No battery power is available.

Option 1: Ensure the batteries are

 

 

installed properly.

 

 

Option 2: Check to see whether the

 

 

DC Breaker has been tripped.

 

 

Option 3: Contact Schneider

 

 

Electric Customer Support (see the

 

 

back cover).