Chapter 5: CPS Appliance Commands | 69 |
|
|
Table 5.34: Show User All Command Display Fields (Continued)
Field
Level
Access
Contents
User’s access level. If a level was not configured, access rights determine the level: Users with SCON access => APPLIANCEADMIN.
Users with USER or PCON but not SCON => ADMIN. Otherwise, USER level is assigned.
User’s access rights and preemption level.
SPC Command
The SPC command changes settings for an SPC device and its sockets.
NOTE: This command configures the port for use with the DSView software. For standalone use of the SPC device, this command should not be used, and the CPS port to which the SPC is attached should be configured as TD=Console.
Access right: SCON or PCON
Access level: ADMIN or APPLIANCEADMIN
Syntax
SPC <port>ALL [MINLOAD=<amps>] [MAXLOAD=<amps>] [SOCKET <socket>ALL] [WAKE=ONOFF] [ONMIN=<time>] [OFFmin=<time>]
Table 5.35: SPC Command Parameters
Parameter | Description | |
|
| |
<port> | Port number in range | |
|
| |
ALL | Indicates that the settings that follow should be applied to all ports configured | |
as SPC. | ||
| ||
|
| |
MINLOAD=<amps> | Minimum load in amperes in the range | |
Default = 0 | ||
| ||
|
| |
MAXLOAD=<amps> | Maximum load in amperes in the range | |
Default = 0 | ||
| ||
|
| |
SOCKET <socket>ALL | Either a socket number on the SPC or All, which indicates that the settings that | |
| follow should be applied to all sockets on the SPC. | |
WAKE=ONOFF | State that the socket will enter when the SPC is powered up. | |
Default = ON | ||
| ||
|
|