D9412GV3/D7412GV3 Program Entry Guide 2.0 Panel and Area Wide Parameters

EN 18

2.3.3Programming Primary and Backup Destinations

Each route number has an R# Primary Device and an R# Backup Device. For example, if two phone numbers are programmed, the R# Primary Device destination is the phone number that the route group attempts to dial first. If the R# Primary Device destination does not connect to the central station receiver after two dialing attempts, the control panel dials the R# Backup Device destination.

You can also program the control panel so that the R# Primary Device or the R# Backup Device uses an SDI device, such as a Network Interface Module.

With enhanced communications, the R# Primary Device destination can be either the phone number or the path number for the SDI device, to which the route group first attempts to send the event. If the R# Primary Device destination fails to connect to the central station receiver after two attempts, the control panel attempts to connect with the R# Backup Device destination.

2.3.4Enhanced Routing

The D9412GV3 and D7412GV3 allow events to be sent to up to four additional SDI Paths. The network interface modules (NIMs) connect directly to the SDI Bus and occupy SDI Address 88 or 92. For additional information regarding the specific programming requirements for enhanced communications, refer to Section 5.5 Programming Path Numbers and IP Addresses for Enhanced Communications on page 131.

2.3.5Programming a Duplicate Report

Select Yes for each available route number to allow an event within a group to send a report to multiple groups. For instance, if fire alarms are programmed for Route Group 1 and Route Group 2, a fire alarm sends a report first to Route Group 1, followed by a duplicate report to Route Group 2.

2.3.6Routing Destination Communication Failures

When the R# Primary Device fails to connect to the central station receiver after two attempts by phone, the R# Backup Device phone number will be dialed. The central station will receive the original event with a COMM TROUBLE PHONE # = (1, 2, 3, or 4) message

added. This event does not occur if there is no backup phone number. If the R# Primary Device is an SDI Path, the central station receives the original event with a COMM TROUBLE RG8 SDI## event modifier. Refer to Table 8 on page 18.

Table 8: SDI Path Number by Device

 

 

 

 

 

Path

1

2

3

4

SDI 88

88

89

90

91

SDI 92

92

93

94

95

When all attempts to both the R# Primary Device and R# Backup Device fail, a COMM FAIL RG# event is generated. COMM RESTORE RG# events are generated when a successful report (via phone or IP) or a successful poll (via IP) is sent over either route within the failed Route Group, even if the report is sent using a different Route Group.

The same COMM TROUBLE conditions occur if the control panel does not receive a positive acknowledgement to a poll from the central station receiver after the configured number of retries. Refer to Path # Poll Rate on page 132.

2.3.7Message Prioritization within a Route Number

The D9412GV3/D7412GV3 Control Panels meet the digital reporting requirements for UL 864. Fire Alarm Events have the highest priority and reports are sent first for each group. Other events are sent in the following order: Panic, Duress, Medical, Intrusion Alarm, Supervisory, and all troubles and restorals.

To comply with NFPA and UL 864 , program Route 1 to send a report of only Fire Alarm Events to ensure the fastest reporting time.

2.3.8Communication Attempts

The control panel makes up to ten communication attempts using the primary and backup devices within a route group. If unsuccessful, it sends a Comm Fail Report. The communication attempts occur in the following sequence:

1.Primary device

2.Primary device

3.Backup device

4.Backup device

5.Primary device

6.Backup device

7.Primary device

8.Backup device

9.Primary device

10.Backup device

When only one destination is programmed, the control panel makes ten attempts to contact that destination. When reporting via phone, each group takes approximately 10 min to go into Comm Fail.

Bosch Security Systems, Inc. 10/11 F01U170807-02

Page 18
Image 18
Bosch Appliances D9412GV3 Programming Primary and Backup Destinations, Enhanced Routing, Programming a Duplicate Report

D9412GV3 specifications

The Bosch Appliances D9412GV3 is a perfect blend of functionality and innovation, designed to meet the needs of modern households. This dishwasher is part of Bosch's reputation for creating high-quality, energy-efficient home appliances. With a sleek design and advanced technology, the D9412GV3 stands out in the crowded market of dishwashers.

One of the main features of the D9412GV3 is its remarkable efficiency. With an Energy Star rating, this model is designed to minimize water and energy consumption while still delivering exceptional cleaning performance. The EcoSense technology optimizes water usage, ensuring every wash cycle is both effective and economical, making it a responsible choice for energy-conscious consumers.

The dishwasher offers a spacious interior, capable of accommodating large loads. Its flexible rack system includes adjustable tines and folding platforms, making it easy to fit various dish sizes, from pots and pans to delicate glassware. Additionally, the third rack feature provides extra space for utensils and smaller items, enhancing its capacity and versatility.

In terms of cleaning power, the D9412GV3 is equipped with the PrecisionWash system. This cutting-edge technology features intelligent sensors that continuously scan and check the load, adjusting the wash cycle as needed for optimal results. Coupled with the 40 dBA noise level, it ensures that the dishwasher operates quietly in the background, so you can enjoy your home without disruptive sounds.

Another standout characteristic is the PureDry technology, an integrated drying system that uses a condensation process to gently dry dishes without the need for extra heat. This not only protects sensitive items but also saves energy, further enhancing the appliance's eco-friendly nature.

Ease of use is a priority for Bosch, as seen in the D9412GV3's user-friendly controls. The intuitive interface allows for selecting various wash cycles and options, including Heavy, Auto, and Quick options, catering to different cleaning needs. Additionally, the Time Delay feature provides the flexibility to set the dishwasher to run at a later time, great for aligning with your schedule.

In summary, the Bosch D9412GV3 combines innovative technologies with a user-centered design to deliver a top-tier dishwasher experience. Its energy-efficient operation, spacious interior, and advanced cleaning features make it an excellent choice for any kitchen, ensuring spotless dishes with minimal effort. With Bosch's commitment to quality, the D9412GV3 stands as a reliable and stylish addition to any modern home.