D9412GV3/D7412GV3 Program Entry Guide 5.0 AUXPARM

EN 139

Perimeter Relay

Default:

No

Selection:

Yes or No

Yes

Change the function of the area-wide

 

fail-to-close relays to follow the

 

perimeter armed states of their

 

areas.

 

 

No

The area-wide fail-to-close relay

 

operates normally.

 

 

When set to Yes, the A# Fail to Close relay becomes an area-wide perimeter armed relay. This relay is activated when all areas assigned to the same relay have perimeter points that are armed.

Early Armed Relay

Default:

No

Selection:

Yes or No

Yes

Change activation of Area Armed or

 

Perimeter Armed Relay to the

 

beginning of the exit delay time.

 

 

No

Maintain the activation of Area

 

Armed or Perimeter Armed Relay at

 

the end of the exit delay time.

 

 

When this prompt is set to Yes, the Area Armed or Perimeter Armed Relay activates at the beginning of the exit delay time.

Daylight Saving Time

Default:

Disabled

Selection:

Disabled or US Calendar

Disabled

The control panel clock is not

 

adjusted for daylight saving time.

US

The control panel clock is adjusted

Calendar

to the US start/end dates for daylight

 

saving.

 

 

5.9Cross Point Parameters

This section discusses the requirements necessary to program Cross Point functions.

Use the Cross Point function on non-fire points only.

The Cross Point option reduces false alarms. Points can be programmed so that the control panel needs to see an Alarm condition within a programmed period of time (called Cross Point Time) from at least two points within a Cross Point Group (Table 38) before Cross Point Alarm Events are generated. These points must have P## Cross Point set to Yes to generate this event.

There are 31 Cross Point Groups in the D9412GV3 and ten in the D7412GV3. Each Cross Point Group consists of eight points and is identified by the point numbers in them (for example, Cross Points 1 to 8, Cross Points 9 to 16, and so on). The maximum number of points that can be programmed to meet the Cross Point criteria is two. Point numbers from different Cross Point Groups do not affect each other. Refer to Table 38 for a complete listing of Cross Points comprising each Cross Point Group.

When any point with P## Cross Point set to Yes detects an alarm condition, the control panel starts a timer as programmed in the Cross Point Time prompt.

If a second Cross Point within the same Cross Point Group detects an alarm condition, the control panel creates a Cross Point Alarm Event for both points, provided both points activate inside the Cross Point Window. A Cross Point is considered to be in alarm when it meets the criteria for Instant Alarm response. The Cross Point index must have P## Pt Response set to a value that generates an instant alarm response.

If a single Cross Point detects an alarm and stays faulted throughout the duration of the Cross Point Window, a standard Alarm Report is generated for that point.

Conversely, if a single Cross Point detects an alarm, then restores, and no other conditions occur, an Unverified Event is generated for that point. A second alarm on the first point does not create an Alarm Event but rather an Unverified Event.

Bosch Security Systems, Inc. 10/11 F01U170807-02

Page 139
Image 139
Bosch Appliances D9412GV3 manual Cross Point Parameters, Perimeter Relay, Early Armed Relay, Daylight Saving Time

D9412GV3 specifications

The Bosch Appliances D9412GV3 is a perfect blend of functionality and innovation, designed to meet the needs of modern households. This dishwasher is part of Bosch's reputation for creating high-quality, energy-efficient home appliances. With a sleek design and advanced technology, the D9412GV3 stands out in the crowded market of dishwashers.

One of the main features of the D9412GV3 is its remarkable efficiency. With an Energy Star rating, this model is designed to minimize water and energy consumption while still delivering exceptional cleaning performance. The EcoSense technology optimizes water usage, ensuring every wash cycle is both effective and economical, making it a responsible choice for energy-conscious consumers.

The dishwasher offers a spacious interior, capable of accommodating large loads. Its flexible rack system includes adjustable tines and folding platforms, making it easy to fit various dish sizes, from pots and pans to delicate glassware. Additionally, the third rack feature provides extra space for utensils and smaller items, enhancing its capacity and versatility.

In terms of cleaning power, the D9412GV3 is equipped with the PrecisionWash system. This cutting-edge technology features intelligent sensors that continuously scan and check the load, adjusting the wash cycle as needed for optimal results. Coupled with the 40 dBA noise level, it ensures that the dishwasher operates quietly in the background, so you can enjoy your home without disruptive sounds.

Another standout characteristic is the PureDry technology, an integrated drying system that uses a condensation process to gently dry dishes without the need for extra heat. This not only protects sensitive items but also saves energy, further enhancing the appliance's eco-friendly nature.

Ease of use is a priority for Bosch, as seen in the D9412GV3's user-friendly controls. The intuitive interface allows for selecting various wash cycles and options, including Heavy, Auto, and Quick options, catering to different cleaning needs. Additionally, the Time Delay feature provides the flexibility to set the dishwasher to run at a later time, great for aligning with your schedule.

In summary, the Bosch D9412GV3 combines innovative technologies with a user-centered design to deliver a top-tier dishwasher experience. Its energy-efficient operation, spacious interior, and advanced cleaning features make it an excellent choice for any kitchen, ensuring spotless dishes with minimal effort. With Bosch's commitment to quality, the D9412GV3 stands as a reliable and stylish addition to any modern home.