WARNING LIST
GSTC Warning | GSP warning | Description of warning: | Troubleshooting |
displayed | displayed |
|
|
|
|
|
|
WARNING | Once the controller activates an ignition module, it will | SEE FAULT LIST | |
IGNITION MODULE X |
| allow 4 minutes for the gas valve to activate. After the trial |
|
FAIL |
| period, if the gas valve has not activated, a fault will be |
|
|
| generated. The module will be locked out and the next |
|
|
| burner will be indexed. |
|
|
|
|
|
WARNING | Should the air proving switch open while the unit is | SEE FAULT LIST | |
AIR PROVING SWITCH X |
| operating this warning is generated. The controller shuts |
|
OPEN WITH |
| down and retries. There are no limits to the amount of times |
|
BLOWERS ACTIVE |
| this warning is generated. |
|
|
|
|
|
WARNING | On startup if the AP switch does not close within the proving | SEE FAULT LIST | |
AIR PROVING SWITCH X |
| period. After 3 tries, a fault will be generated. |
|
OPEN WITH |
|
|
|
BLOWERS ACTIVE |
|
|
|
WARNING | If a blower RPM is above the RPM tolerance limit this | SEE FAULT LIST | |
BLOWER X |
| warning is generated. If it is above the RPM tolerance limit |
|
RPM HIGH |
| for more than 10 seconds a fault will be generated. |
|
|
|
|
|
WARNING | If a blower RPM is below the RPM tolerance limit this | SEE FAULT LIST | |
BLOWER X |
| warning is generated. If it is below the RPM tolerance limit |
|
RPM LOW |
| for more than 10 seconds a fault will be generated. |
|
|
|
|
|
WARNING | HMW | In the user menu the user sets the maintenance time. Once | SEE FAULT LIST |
MAINTENANCE TIME |
| this time expires this warning is displayed. The maintenance |
|
HAS ELAPSED |
| time is measured in weighted operational hours. |
|
|
| With switch 5, #4 activated, this warning will remain until |
|
|
| the warning is reset in the User level |
|
|
|
|
|
WARNING | Low water level has not been reached within expected time | SEE FAULT LIST | |
Too LONG TO FILL |
| interval during initial fill sequence. Unit will continue filling |
|
|
| while warning is displayed. A Water Fill Fail fault will be |
|
|
| generated if the low water level is not reached after an |
|
|
| additional length of time. |
|
|
|
|
|
WARNING | Keep warm feature has initiated combustion sequence at | ||
KEEP WARM ACTIVE |
| 75% output. This occurs when keep warm feature has been | will stop being |
SYSTEM DEMAND |
| activated via | displayed once tank |
ACTIVATED AT 75% |
| below minimum and the tank temperature sensor is | temperature sensor |
|
| registering cold (open contacts). | indicates water is |
|
|
| warm |
|
|
| |
|
|
| can be disabled using |
|
|
|