WARNING LIST

WARNING LIST

GSTC Warning

GSP warning

Description of warning:

Troubleshooting

displayed

displayed

 

 

 

 

 

 

WARNING

IMW-X

Once the controller activates an ignition module, it will

SEE FAULT LIST

IGNITION MODULE X

 

allow 4 minutes for the gas valve to activate. After the trial

 

FAIL

 

period, if the gas valve has not activated, a fault will be

 

 

 

generated. The module will be locked out and the next

 

 

 

burner will be indexed.

 

 

 

 

 

WARNING

APW-X

Should the air proving switch open while the unit is

SEE FAULT LIST

AIR PROVING SWITCH X

 

operating this warning is generated. The controller shuts

 

OPEN WITH

 

down and retries. There are no limits to the amount of times

 

BLOWERS ACTIVE

 

this warning is generated.

 

 

 

 

 

WARNING

AOW-X

On startup if the AP switch does not close within the proving

SEE FAULT LIST

AIR PROVING SWITCH X

 

period. After 3 tries, a fault will be generated.

 

OPEN WITH

 

 

 

BLOWERS ACTIVE

 

 

 

WARNING

BHW-X

If a blower RPM is above the RPM tolerance limit this

SEE FAULT LIST

BLOWER X

 

warning is generated. If it is above the RPM tolerance limit

 

RPM HIGH

 

for more than 10 seconds a fault will be generated.

 

 

 

 

 

WARNING

BLW-X

If a blower RPM is below the RPM tolerance limit this

SEE FAULT LIST

BLOWER X

 

warning is generated. If it is below the RPM tolerance limit

 

RPM LOW

 

for more than 10 seconds a fault will be generated.

 

 

 

 

 

WARNING

HMW

In the user menu the user sets the maintenance time. Once

SEE FAULT LIST

MAINTENANCE TIME

 

this time expires this warning is displayed. The maintenance

 

HAS ELAPSED

 

time is measured in weighted operational hours.

 

 

 

With switch 5, #4 activated, this warning will remain until

 

 

 

the warning is reset in the User level

 

 

 

 

 

WARNING

UNW-6

Low water level has not been reached within expected time

SEE FAULT LIST

Too LONG TO FILL

 

interval during initial fill sequence. Unit will continue filling

 

 

 

while warning is displayed. A Water Fill Fail fault will be

 

 

 

generated if the low water level is not reached after an

 

 

 

additional length of time.

 

 

 

 

 

WARNING

UNW-C

Keep warm feature has initiated combustion sequence at

-Warning message

KEEP WARM ACTIVE

 

75% output. This occurs when keep warm feature has been

will stop being

SYSTEM DEMAND

 

activated via dip-switch settings, the system demand is

displayed once tank

ACTIVATED AT 75%

 

below minimum and the tank temperature sensor is

temperature sensor

 

 

registering cold (open contacts).

indicates water is

 

 

 

warm

 

 

 

-Keep warm feature

 

 

 

can be disabled using

 

 

 

dip-switch settings