Nortec Industries GS Series manual FTBD Hour, Blowdown Rate, Float Check

Models: GS Series

1 78
Download 78 pages 6.36 Kb
Page 61
Image 61
FTBD Hour

FTBD Hour

Works in conjunction with FTBD hours.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DATE/TIME/UNITS

 

 

 

 

 

 

 

 

 

 

 

 

 

FTBD HOURS

XXX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LANGUAGE CONTROLS

 

 

 

 

 

 

 

 

 

 

 

 

 

FTBD HOUR

XX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATER MANAGEMENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOWDOWN RATE

XX%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLOAT CHECK

HH:MM

 

0335

CONTROL TYPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FILL CORRCTN

XX%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAPACITY LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRAIN CORRCTN

XX%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CALIBRATE

 

 

 

 

 

 

 

 

DRAIN COOL:

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOWDOWN RATE CHANGE VALUE XX% STEAM OUTPUT

Here the user sets the time of day (24 hour format) when they want the FTBD to execute. The time can be set to trigger the cycle during off hours, when the humidity requirements are minimal.

The time is adjusted in one-hour increments.

Blowdown Rate

This parameter adjusts the frequency of blowdown cycles.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DATE/TIME/UNITS

 

 

 

 

 

 

 

 

 

 

 

 

 

FTBD HOURS

XXX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LANGUAGE CONTROLS

 

 

 

 

 

 

 

 

 

 

 

 

 

FTBD HOUR

XX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATER MANAGEMENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOWDOWN RATE

XX%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLOAT CHECK

HH:MM

 

0335

CONTROL TYPE

 

 

 

 

 

 

 

 

 

 

FILL CORRCTN

XX%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAPACITY LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRAIN CORRCTN

XX%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CALIBRATE

 

 

 

 

 

 

 

 

DRAIN COOL:

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLOAT CHECK CHANGE VALUE HH:MM

Depending on water quality, the blowdown rate can be adjusted from 5% to 50%. The percentage is based on the steam production rate i.e. a 10% BD rate will drain 10 kg. of water for every 100 kg. of steam produced.

The higher the mineral content of the water the higher the BD rate should be set.

Float Check

This parameter sets the time of day the controller will force a float check.

Float checks are important to ensure the water level detection system is operating correctly. The float check also tests the fill and drain system and will report any problems detected.

To set the time of day, highlight the selection then enter the user code (0335). Press enter. Use the UP/DOWN arrows to adjust the hours (24 hour format). Pressing enter saves the setting and indexes the display to minutes. Use the UP/DOWN arrows to adjust the minutes. Pressing enter saves the setting and returns the user to the previous menu.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DATE/TIME/UNITS

 

 

 

 

 

 

 

 

 

 

 

 

FTBD HOURS

XXX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LANGUAGE CONTROLS

 

 

 

 

 

 

 

 

 

 

 

 

FTBD HOUR

XX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATER MANAGEMENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOWDOWN RATE

XX%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLOAT CHECK

HH:MM

 

0335

CONTROL TYPE

 

 

 

 

 

 

 

 

 

 

FILL CORRCTN

XX%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAPACITY LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRAIN CORRCTN

XX%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CALIBRATE

 

 

 

 

 

 

 

 

DRAIN COOL:

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRAIN COOL: ON

OFF SMART

- 57-

Page 61
Image 61
Nortec Industries GS Series manual FTBD Hour, Blowdown Rate, Float Check