Nortec Industries GS Series manual Figure #18 GasPiping, Exhaust Venting- Outdoor Units

Models: GS Series

1 78
Download 78 pages 6.36 Kb
Page 24
Image 24
Figure #18

Figure #18

GasPiping

system can be damaged is by the failure of both devices.

EXHAUST VENTING - OUTDOOR UNITS

￿All required exhaust venting is provided with each GS Outdoor model, by Nortec, including rain cap and storm collar. All venting components external to the unit are shipped with the unit and must be installed on site. Refer to Figure #19 for venting components.

Figure #19

Exhaust - Outdoor Units

Rain Cap

All Venting provided by Nortec

Extension Pipe

Storm Collar

￿Each vent length and the rain cap have a built-in mechanical locking band and gasket. Simply push together each component to the stop bead, which provides an air & water-tight seal. Then tighten the integrated locking band on each component to complete the installation of the exhaust venting.

￿The rain cap must extend at least 2 feet above any ridge within 10 feet of the unit. The exhaust venting can be extended using additional vent lengths purchased from Nortec.

ELECTRICAL INSTALLATION

￿Power and control wiring is to be routed into the humidifier through the pipe chase in the base pan of the outdoor models located in the burner area.

￿Installation details for primary and low voltage control wiring are the same as for indoor units.

￿A field supplied NEMA rated weatherproof disconnect switch must be mounted external to the GS Outdoor unit to allow for power interruption during servicing and/or maintenance. A mounting plate, located on the front of each outdoor model above the electrical access door, is available for mounting of the disconnect switch. Two electrical conduits are provided for routing the primary wiring to the disconnect switch and then back inside the enclosure to the main power terminal strip. See Figure #20 for details.

Figure #20

Electrical Box

Disconnect box

(By others)

Primary wiring

(By others)

- 20 -