Nortec Industries GS Series manual Gs Series External Controls Wiring Connections, 3 4

Models: GS Series

1 78
Download 78 pages 6.36 Kb
Page 18
Image 18
GS SERIES

GS SERIES

EXTERNAL CONTROLS WIRING CONNECTIONS

LOW VOLTAGE TERMINAL STRIP

NOTE: This is a generic wiring diagram only. For specific wiring instructions, it is necessary to refer to the wiring diagram which is supplied with each unit.

WA R N I N G : F a i l u r e t o w i r e t h e c o n t r o l l e r i n a c c o r d a n c e w i t h t h e w i r i n g d i a g r a m t h a t w a s s u p p l i e d

w i t h t h e u n i t c o u l d p e r m a n e n t l y d a m a g e t h e G S T C / G S P b o a r d . S u c h e r r o r s w i l l v o i d t h e u n i t w a r r a n t y.

Security Loop

EXTERNAL

1 2

INTERNAL

ModulationInputSignal“A"

ModulationInputSignal“B”

10Vdcoutput

FullTankBlowDown(FTBD) enable(24Vac)

SafetyInterrupt(24Vac)

Humidifier“ON”

 

Humidifier“ACTIVE”

 

Humidifier“SERVICE”

 

 

Humidifier“FAULT”

 

 

 

 

 

 

 

 

 

 

COM

N.O.

COM

N.O.

COM

N.O.

N.O.

COM

N.C.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 LOW VOLTAGE TERMINAL STRIP3  4  5  6  7  8  9 10 11 12 13 14 15 16 17 18 4 Low Voltage Terminal Strip 5 Manual background 6 Manual background 7 Manual background 8 Manual background 9 Manual background10Manual background 11Manual background 12Manual backgroundManual background 13Manual background 14Manual background 15Manual background 16Manual background 17Manual background 18

+ +

EXTERNAL

INTERNAL

NOTE: If no On/Off Control is used then a field jumper must be connected across terminals 1 and 2 in order for the humidifier to operate.

Low Voltage Terminal Strip

1 & 2: Wire all on/off controls and safeties between these two terminals. If not used, jumper 1 & 2 for the unit to operate.

4:Modulating input to humidifier “A”.

5:Modulating input to humidifier “B”.

6:10 Vdc output.

8:When 24 Vac input received, the unit will initialize a full tank blowdown.

9:Safety interrupt (24 Vac).

10 & 11: Remote indication connection for humidifier “on” status indication.

12 & 13: Remote indication connection for humidifier “active” status.

14 & 15: Remote indication connection for service required indication.

16 & 17 & 18: Remote indication connection for fault indication.