FAULT LIST

FAULT LIST

GSTC fault

GSP fault code

Description of fault

Troubleshooting

displayed

displayed

 

 

 

 

 

 

FAULT

NBF

Once the GS controller detects an ignition

-Check red LED’s on all modules for

NO BURNERS

 

module fail, it will index to the next available

flashing fault code

AVAILIBLE

 

ignition module. If all ignition modules have

-Ensure there is gas supply to the

 

 

failed or there are none available (in the case of

humidifier

 

 

a 100 unit) this fault will be generated

-Ensure that the burners have not been

 

 

 

disabled in the software

 

 

 

-Consult factory

 

 

 

 

FAULT

AOF-X

On startup after 3 tries if the AP switch does

-Check that blue hoses on the Air

AIR PROVING

 

not close within the proving period, this fault

Proving switch have not come loose.

SWITCH X OPEN

 

will be generated

-Check that wires on the Air Proving

WITH

 

 

switch are on the N/O contacts

BLOWERS ACTIVE

 

 

-If available, swap Air Proving switch

 

 

 

with another and see if the fault follows

 

 

 

the air proving switch, if so, replace

 

 

 

switch

 

 

 

-Consult factory

FAULT

ACF-X

On initial startup if any of the A/P switches are

-Ensure that wiring on the air proving

AIR PROVING

 

closed this fault will be generated.

switch is on the N/O contacts

SWITCH X

 

 

-Ensure that there is no continuity

CLOSED WITH

 

 

between the switch with the wires off,

BLOWERS

 

 

if so replace switch

INACTIVE

 

 

-Ensure that there is not a strong

 

 

 

positive pressure in the room holding

 

 

 

the switch closed

 

 

 

-Consult factory

 

 

 

 

FAULT

BHF-X

If the blower RPM is above the RPM tolerance

-Check wiring to lead blower and

BLOWER X

 

for more than 10 seconds, this fault is

ensure a good connection.

RPM HIGH

 

generated and the humidifier stops.

-Check lead blower for any restrictions

 

 

 

by testing it in the diagnostics screen.

 

 

 

-Consult factory

FAULT

BLF-X

If the blower RPM is below the RPM tolerance

-Check wiring to blower X and ensure

BLOWER X

 

for more than 10 seconds, this fault is

a good connection.

RPM LOW

 

generated and the humidifier stops

-Check blower X for any restrictions by

 

 

 

testing it in the diagnostics screen.

 

 

 

-Consult factory

FAULT

BNF-X

On startup, if the blower RPM does not exceed

-Ensure there is power to the blower

BLOWER X

 

500 RPM within 5 seconds or if during

and that all wires are making a proper

NOT OPERATIONAL

 

operation, the RPM drops below 500 RPM for

connection.

 

 

more than 5 seconds this fault is generated

-Consult factory

 

 

 

 

FAULT

GVF-X

If the controller detects that a gas valve has

-Ensure that the ignition module is not

ILLEGAL GAS

 

activated at a time it should not this fault is

miswired or that the module is not

VALVE

 

Generated.

faulty by swapping it with a known

BURNER X

 

 

good one. If the problem follows the

 

 

 

ignition module, replace the module

 

 

 

-Consult factory

 

 

 

 

- 60 -