Fill CORRCTN (correction)

Fill CORRCTN (correction)

Used for adjusting the fill rate. Adjustments to be made under factory direction only.

Drain CORRCTN (correction)

Used for adjusting the drain rate. Adjustments to be made under factory direction only.

Drain Cool

The customer can select the type of drain water tempering they require (depending on local plumbing codes)

The customer can select ON, OFF, or SMART.

ON – whenever the drain valve is activated through software, the fill valve will automatically activate. This is the factory default setting, but is the most wasteful of water since it will activate even if the drain water is cool.

OFF – The drain water is never tempered. This can be used where plumbing codes permit. Some process waters are very expensive, so the customer may choose to temper the drain water through other means.

SMART – The humidifier has a tank sensor that communicates the water temperature to the controller. If the water is hot during drain cycles the fill valve will be activated. This is the most “water smart” of the settings.

Drain CORRCTN (correction) DATE/TIME/UNITS

LANGUAGE CONTROLS

WATER MANAGEMENT

Drain Cool CONTROL TYPE

CAPACITY LIMIT

CALIBRATE

Control Input CONTROL TYPE CONTROL INPUT TRANSDUCER INPUT

Manual background0335Manual background

CONTROL TYPE CONTROL INPUT Manual background TRANSDUCER INPUT

Control Input

This section is used for configuring the controller for a controller input or a transducer input.

To select control input, highlight the selection then enter the user code (0335). Press enter. Use the UP/DOWN arrows to select control input.

The controllers dip switches then determine the type (0-10 Vdc, 0-20 mA, etc.) of control signal to process.

- 58 -